Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T18CM01145
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/08/2018 | LPEREZ2 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
05/08/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 31. Plan Sheet E1.0 not sealed by Registrant. #2. Provide shielding information for the proposed new luminaires. #3. Identify the 30 KVA transformer on plan sheet E3.0. #4. Indicate if the receptacles are GFI protected. Ref: 2012 IBC Sec 107.2.1, 2011 NEC |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/08/2018 | LPEREZ2 | OUT TO CUSTOMER | Completed |