Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM01145
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment; Sheet S3.0; Light Pole Foundation Detail: The height of the light (maximum) and the foundation size and reinforcing must be designed and detailed before this permit can be approved. Please provide structural calculations for the light pole and indicate on the detail the foundation information. The response to this comment is that the pole foundation detail on Sheet S3.0 was deleted, and the detail on Sheet E1.0 is to be used as referenced by the City of Tucson Light Pole Standards. In discussion with the electrical plans examiner, he was not aware of any section in the 2011 NEC that designs light pole foundations. Please clarify where this section is located in the NEC, and indicate the basis for the pole foundation shown on Sheet E1.0. |
| 03/14/2018 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 03/14/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | As per the previous review it was reqested to provide compliance with the Tucson /Pima County Outdoor Lighting Code. The applicant is appealing to the Chief Building Official for a lighting variance. |
| 03/15/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 03/15/2018 | ANDREW CONNOR | ZONING | REVIEW | Approved |