Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM01145
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. The panel marks or identification does not correlate with the one line diagram. #2. Provide full compliance with the Tucson/Pima County Outdoor Lighting Code. #3. The current NEC is 2011 not 2014. (Electrical Notes) #4. Provide a grounding detail for the 30 KVA transformer. Ref:2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code |
| 02/15/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S1.0; General Structural Notes (Foundations): Please provide one copy of the soils report for review. 2. Sheet S3.0; Light Pole Foundation Detail: The height of the light (maximum) and the foundation size and reinforcing must be designed and detailed before this permit can be approved. Please provide structural calculations for the light pole and indicate on the detail the foundation information. |
| 02/15/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/07/2018 | KROBLES1 | ENGINEERING | REVIEW | Needs Review | |
| 03/07/2018 | KROBLES1 | FIRE | REVIEW | Needs Review | |
| 03/07/2018 | KROBLES1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/07/2018 | KROBLES1 | OUT TO CUSTOMER | Completed |