Permit Number: T18CM01061
Parcel: 12501092A

Address:
2929 E 6TH ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM01061
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1, Provide a detailed single site plan showing all the buildings, canopies, location of the service equipment used for the PV Interconnection, and associated PV equipment. Include the building and canopy identifications or numbers.
#2. Provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting. If you are claiming exemption for lumen calcs per sec 104.2.1 (Exception), provide evidence that the luminaires have full cut off shielding and lamp source color temperature does not exceed 3500K.
#3. Provide and a letter from the manufacturer of the electric service equipment (including a contact person) stating that the proposed line side bus tap utilizing existing holes located in the distribution section will not compromise the listing or compromise the performance of the equipment. Otherwise provide for a NRTL field inspection to re-list the equipment.
Ref: 2012 IBC 107.2.1, 2011 NEC 110.3b, The City Tucson Commercial Plan Submittal Requirements, The Tucson/Pima County Outdoor Lighting Code.
03/23/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T1: Please provide a site plan that clearly identifies the eight new parking structures (Canopies 1 through 8) and indicates the module layout on each canopy. Provide the dimensions from each new canopy to adjacent buildings, property lines, and other canopies as required.
2. General: Please provide a written response to the review comment.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/26/2018 BLARSON1 OUT TO CUSTOMER Completed