Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM01060
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1, Provide a detailed single site plan showing all the buildings, canopies, location of the service equipment used for the PV Interconnection, and associated PV equipment. Include the building and canopy identifications or numbers. #2. Provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting. If you are claiming exemption for lumen calcs per sec 104.2.1 (Exception), provide evidence that the luminaires have full cut off shielding and lamp source color temperature does not exceed 3500K. #3. Provide and a letter from the manufacturer of the electric service equipment (including a contact person) stating that the proposed line side bus tap utilizing existing holes located in the distribution section will not compromise the listing or compromise the performance of the equipment. Otherwise provide for a NRTL field inspection to re-list the equipment. Ref: 2012 IBC 107.2.1, 2011 NEC 110.3b, The City Tucson Commercial Plan Submittal Requirements, The Tucson/Pima County Outdoor Lighting Code. |
| 03/23/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet T1: Please provide a site plan that clearly identifies the three existing structures (Buildings 3, 4, and 6), and reference Sheet A2 for the module layouts. 2. Sheet A2; Building 6 Layout: The title indicates 93 modules, while the plan review card indicates 103. Please verify. 3. General: Please provide written responses to all review comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/26/2018 | BLARSON1 | OUT TO CUSTOMER | Completed |