Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM01032
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 3; Sheet A0.11; Plumbing Fixture Calculations: Please add a reference on this sheet to see the plumbing drawings for the specification of the point of use water dispenser. 2. Sheet A2.11; Ground Floor Plan: Please indicate the location of the single point of use water dispenser on the plan, and reference the plumbing drawings for the specification of that dispenser. 3. Previous Comment 12; Lettering Requirement: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Sheet A0.21 (Code Plan), Sheet A2.10 (Keynotes/General Notes), Sheet A2.11 (Keynotes/General Notes), Sheet A2.12 (Keynotes), Sheet A2.41 (Keynotes), Sheet A3.11 (Keynotes), Sheet A5.11 (Section 1), and Sheet A8.11 (Schedules/Legends) do not meet that requirement. Please revise. 4. General: Please provide written responses to all review comments. |
| 03/23/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a metering faucet for the revised lavatory. The faucet shakll deliver no more than 0.25 gallons per cycle and each cycle shall last for more than 10 seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. |
| 03/23/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. As requested per the previous plan review comment #1,"Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code". Section 104.2 states that evidence must be provided on the plan documents that the proposed work will comply with this code. (a) Indicate the lighting area and option used from table 401.1. Include lumen calcs allowed vs total lumens proposed including any existing luminaires. (b) Provide compliance with 402.1 for lamp source color temperature for all the exterior luminaires. |
| 03/23/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the heating and cooling load calculations, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson. 2. Correct the entries in the heat pump schedule for the cooling capacity. |