Permit Number: T18CM00998
Parcel: 133180080

Address:
1057 N KOLB RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM00998
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a metering faucet that dispenses a maximum of 0.25 gallons per cycle (i.e. not 0.25 GPM). [Initial comment: Provide specifications for the proposed lavatory, faucet, and water closet.]
2. Revise the new detail to show the installation of the required thermostatic mixing valve. [Initial comment: Provide a detail showing how the proposed water heater is to be installed, including the mounting platform, safety pan with drain, T&P relief piping, expansion tank, and vacuum relief valve.]
02/12/2018 ROBERT SHERRY WATER REVIEW Completed
02/12/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The exhaust fan shall run whenever the supply diffuser is introducing air into the restroom. Since the diffuser is required to continuously supply air during the hours of operation, the exhaust fan shall also operate on the same schedule. [Initial comment: Provide the sequence of operation for the exhaust fan.]