Permit Number: T18CM00998
Parcel: 133180080

Address:
1057 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM00998
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2018 ALEXANDRA HINES ZONING REVIEW Approved
02/08/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify that the proposed 6" duct will accommodate the 300 CFM flow rate with the specified exhaust fan.
2. Provide the sequence of operation for the exhaust fan.
02/08/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/08/2018 AHINES2 ENGINEERING REVIEW Passed
02/08/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide specifications for the proposed lavatory, faucet, and water closet.
2. Provide a detail showing how the proposed water heater is to be installed, including the mounting platform, safety pan with drain, T&P relief piping, expansion tank, and vacuum relief valve.
02/08/2018 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the size and serial number of the water meter serving this suite.
2. Provide the size and location of the backflow preventer for this suite.
02/08/2018 JPEELDA1 FIRE REVIEW Approved
02/12/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Completed
02/12/2018 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/12/2018 KROBLES1 APPROVAL SHELF Completed
02/12/2018 KROBLES1 OUT TO CUSTOMER Completed
02/12/2018 KROBLES1 REJECT SHELF Completed