| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/08/2018 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
| 02/08/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the proposed 6" duct will accommodate the 300 CFM flow rate with the specified exhaust fan. 2. Provide the sequence of operation for the exhaust fan. |
| 02/08/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/08/2018 | AHINES2 | ENGINEERING | REVIEW | Passed | |
| 02/08/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide specifications for the proposed lavatory, faucet, and water closet. 2. Provide a detail showing how the proposed water heater is to be installed, including the mounting platform, safety pan with drain, T&P relief piping, expansion tank, and vacuum relief valve. |
| 02/08/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Provide the size and serial number of the water meter serving this suite. 2. Provide the size and location of the backflow preventer for this suite. |
| 02/08/2018 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 02/12/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 02/12/2018 | KROBLES1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |