Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM00980
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/21/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
05/24/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. This is the third electrical review. As before there was no written response to the electrical review comments found in the re-submittal. Also the plans do not reflect any changes or corrections. It was observed however that the note in the existing distribution panel calls out for a 225 amp circuit breaker to be installed to feed the new panel 'PK3'. The circuit breaker shown at the bottom of the distribution panel feeding 'PK3' is still shown as a 250 amp breaker. Also previous comment #1 was not addressed. Dan.santacruz@tucsonaz.gov |