Permit Number: T18CM00980
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM00980
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/24/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
This is the third electrical review. As before there was no written response to the electrical review comments found in the re-submittal. Also the plans do not reflect any changes or corrections. It was observed however that the note in the existing distribution panel calls out for a 225 amp circuit breaker to be installed to feed the new panel 'PK3'. The circuit breaker shown at the bottom of the distribution panel feeding 'PK3' is still shown as a 250 amp breaker. Also previous comment #1 was not addressed.