Review Details: RESUBMITTAL

Permit Number - T18CM00980
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/26/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Locating the hub drain behind an under-counter refrigerator on castors does not meet the requirements of ready access. Reference: Section 202, IPC 2012 (definition of ready access). [Initial comment: Indirect waste receptors (e.g. hub drains) shall not be installed in a closet or cupboard, or unventilated space. Ready access shall be provided to all indirect waste receptors. Reference: Section 802.3, IPC 2012.]
2. The hand sink (item #1) does not seem to appear on the waste and vent riser diagram. Reference: Section 301.3, IPC 2012.
05/08/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change The electrical review comment responses submitted are not addressed to the correct comments. The comments from the last electrical review are as follows,"Please address the following electrical plan review comments. Also provide a wriien response.
#1. Identify the distribution panel feeding the New panel 'PK3'.
And provide a complete panel schedule including load calcs for this panel.
#2. The OCPD (250 amps) in the distribution panel that is feeding the new panel 'PK3' is ovesized. Should be 225 amps max. NEC 408.36.
Ref: 2012 IBC sec 107.2.1, 2011 NEC".
Please address the correct comments and revise the electrical plans accordingly.