Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM00980
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM00980
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2018 JPEELDA1 FIRE REVIEW Approved
02/22/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please indicate on the drawings the accessibility requirements of the ICC/ANSI A117.1-2009 are met for sales and service counters (Section 904), including counter heights and counter approaches. Please include the specific requirements in the note.
02/27/2018 ROBERT SHERRY WATER REVIEW Completed
02/27/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, safety pan, and valves. Reference: Sections 503, 504, 606.1, and 607.3, IPC 2012.
2. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference: Section C404.4, IECC 2012.
3. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/h F on the first 8 feet of supply and discharge piping. Reference: Section C404.5, IECC 2012.
4. Provide a schedule for the water and drain connection requirements of the proposed appliances. Reference: Section 107.2.1, IBC 2012.
5. Appliances (e.g. soda dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. At a minimum, beverage dispensers require the use of a backflow preventer listed to ASSE 1022. Reference: Sections 608.1, 608.3, and 608.16.10, IPC 2012.
6. Verify that any proposed backflow preventers with atmospheric vents are accessible for inspection, maintenance and that water leakage will not cause damage. Reference: Section 608.14, IPC 2012.
7. Provide for sterilization and testing of the domestic water system per Section 610, IPC 2012.
8. Verify the materials proposed for waste and vent piping are acceptable to the property owner. Reference: Section 702, IPC 2012.
9. Finish drawing the waste and vent isometrics, showing how the new drainage piping will connect to the existing drainage piping. Reference: Section 107.2.1, IBC 2012.
10. Provide cleanouts for all horizontal drains; the cleanouts shall be sized per Section 708.7, IPC 2012 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.1 and 708.5, IPC 2012.
11. Indirect waste receptors (e.g. hub drains) shall not be installed in a closet or cupboard, or unventilated space. Ready access shall be provided to all indirect waste receptors. Reference: Section 802.3, IPC 2012
12. Clarify how the drainage system is to be vented in accordance with at least one of the methods shown in Chapter 9, IPC 2012.
13. Provide a detail of the proposed loop venting. Note that loop venting (i.e. island fixture venting) is not allowed for fixtures other than sinks or lavatories. Reference: Section 916, IPC 2012.
14. Provide data showing that the proposed running traps (also known as building traps) are self-scouring and installed in accordance with the requirements of the 2012 IPC. Reference: Sections 1002.1, 1002.2, 1002.4, and 1002.6, IPC 2012.
15. Provide additional details regarding the CO2 system. If the system contains 100 pounds or more of CO2, specific requirements apply, including details involving ventilation, piping, and detection/alarms.
02/27/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/06/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a wriien response.
#1. Identify the distribution panel feeding the New panel 'PK3'.
And provide a complete panel schedule including load calcs for this panel.
#2. The OCPD (250 amps) in the distribution panel that is feeding the new panel 'PK3' is ovesized. Should be 225 amps max. NEC 408.36.
Ref: 2012 IBC sec 107.2.1, 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2018 LPEREZ2 APPROVAL SHELF Completed
03/08/2018 LPEREZ2 OUT TO CUSTOMER Completed
03/08/2018 LPEREZ2 REJECT SHELF Completed