Permit Number: T18CM00892
Parcel: 10707012C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM00892
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2018 MARTIN BROWN FIRE REVIEW Approved
02/08/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/12/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref: line diagrams:
(a) Provide voltage, Phase, AIC rating, GEC conductor size and type, Grounding electrode.
(b) Note for the new 400 amp service states,"SOLAR READY OR EQUIVALENT". Please be more specific.
(c) Ref: Site Plan. Locate the Inverters, utility disconnect, PV meter, on the site plan.
Ref; 2012 IBC sec 107.2.1, 2011 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2018 KROBLES1 OUT TO CUSTOMER Completed