Review Details: COMMERCIAL - TI
Permit Number - T18CM00844
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/02/2018 | MCASTRO2 | ZONING | REVIEW | Approved | |
| 02/02/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide source capture exhaust at locations where nail polish is applied. 2. Do not recirculate air from a nail salon to other occupancies. |
| 02/02/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/02/2018 | MCASTRO2 | ENGINEERING | REVIEW | Passed | |
| 02/02/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide backflow protection for each pedicure chair (HW & CW) 2. Show a dirt leg on the gas line feeding the water heater in detail 201 |
| 02/02/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/02/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 02/06/2018 | QJONES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 02/06/2018 | QJONES1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |