Review Details: COMMERCIAL - TI

Permit Number - T18CM00812
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/01/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/01/2018 ACONNOR1 ENGINEERING REVIEW Passed
02/01/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/01/2018 MARTIN BROWN FIRE REVIEW Approved
02/01/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide temperature mixing valves for the restroom lavatories that complies with ASSE 1070.
02/01/2018 ROBERT SHERRY WATER REVIEW Completed
02/01/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet CV.0; Building Codes: Please include the 2009 ICC/ANSI A117.1 accessibility code in this list.
2. Sheet A1.0; Floor Plan: Per the ICC/ANSI Section 1108.2.9.1, 5% of dining surfaces and seating must be accessible. Please indicate on the plan the location of these tables and seats.
3. Sheet A2.0; Sections 4 and 13: Please provide the size and spacing of the wall studs. If these are on the Decor Drawings, please provide those drawings for review.
4. Sheet A2.0; Service Counter Plan: At this counter, the ICC/ANSI Section 904.3 indicates the requirements for counter heights and approaches. Please indicate on this plan (or the plan on Sheet A1.0) the location of this counter and the requirements.
5. General: Please provide written responses to all review comments.