Permit Number: T18CM00807
Parcel: 140160090

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM00807
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/01/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/01/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/01/2018 ROBERT SHERRY WATER REVIEW Completed
02/01/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Floor Plan: Please add a wall type indicator to the east wall (Keynote 7).
2. Sheet A2.0; Restroom Elevations: Elevation A needs the dimension of the horizontal grab bar from the back wall. See the ICC/ANSI Figure 604.5.1.
3. Sheet S1.0; Roof Plan: The Roof Plan and General Notes indicate there are structural calculations for this project. Please provide.
4. General: Please provide written responses to all review comments.
02/01/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/02/2018 JVINCEN1 FIRE REVIEW Approved
02/05/2018 KROBLES1 ZONING REVIEW Needs Review
02/05/2018 KROBLES1 ENGINEERING REVIEW Needs Review