Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM00807
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/01/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/01/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
02/01/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/01/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
02/01/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0; Floor Plan: Please add a wall type indicator to the east wall (Keynote 7). 2. Sheet A2.0; Restroom Elevations: Elevation A needs the dimension of the horizontal grab bar from the back wall. See the ICC/ANSI Figure 604.5.1. 3. Sheet S1.0; Roof Plan: The Roof Plan and General Notes indicate there are structural calculations for this project. Please provide. 4. General: Please provide written responses to all review comments. |
02/01/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
02/02/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
02/05/2018 | KROBLES1 | ZONING | REVIEW | Needs Review | |
02/05/2018 | KROBLES1 | ENGINEERING | REVIEW | Needs Review |