Permit Number: T18CM00781
Parcel: 10609043B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM00781
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S2.6 (Drilled Pier Depth Table); Structural Calculations (Sheet 5.3.1): The calculations indicate a minimum depth of 7'-5" (7.43'), while the table on Sheet S2.6 indicates 7'-3" (for constrained analysis). Please coordinate.
02/23/2018 ROBERT SHERRY WATER REVIEW Passed
02/28/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/06/2018 KROBLES1 OUT TO CUSTOMER Completed