Permit Number: T18CM00718
Parcel: 113070060

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T18CM00718
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2018 MARTIN BROWN FIRE REVIEW Approved
04/04/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/05/2018 ROBERT SHERRY WATER REVIEW Completed
04/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The comment response refers to an attached application for exemption from mechanical ventilation but no such application was found with the submittal. See https://www.tucsonaz.gov/files/pdsd/forms/Appeal_form4.pdf [Initial comment: Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012.]
04/09/2018 DAVID RIVERA ZONING REVIEW Approved