Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM00718
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/31/2018 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Per the 2012 IFC, section 1008.1.10 Panic hardware is required in a A occupancy with the load above 50. Please indicate on sheet I-1103A that panic hardware will be installed. |
| 02/08/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G-0005; Work Plan: Accessibility Key G indicates the barrier free path of travel. Please reference Sheet G-0006 for the exit access travel distance on each of those paths. 2. Sheet G-0006; Safety Plan: Please indicate on the drawing the number of occupants that will exit at each door (using the exit access travel distance paths). 3. Sheet G-0006; Egress Width Analysis: The analysis indicates 35 occupants. The table indicates 50 occupants in the interior. Please revise the exit width analysis. 4. Sheet I-1103; Detail 3: Please indicate the concrete curb thickness on the detail. 5. Sheet I-1103 (Floor Plan); Sheet I-1103A (Interior Door Schedule): The floor plan indicates a door 10190 into the women's restroom. The floor plan on Sheet I-1105 indicates two water closets in that restroom, while the Door Schedule indicates door 10190 has a lock. Should this door have a lock when there are two water closets in the room? Please verify and revise as required. 6. Sheet I-1103 (Floor Plan); Sheet I-1103A (Interior and Exterior Door Schedule): The unnamed room adjacent to the workroom has an exterior door on the west wall marked 10190, and is indicated in the Exterior Door Schedule. Is this door mismarked (the interior restroom doors are also marked as 10190)? Please verify and revise as required. 7. Sheets I-1107, 1107A, and 1107B: Please include the height of all counters (on the plan, in the Casework Schedule, or on the Interior Elevation Sheets I-2101, 2102, or 2103) that are required to be accessible per the ICC/ANSI Section 904. 8. Sheet I-1108; Details 3 and 4: Please indicate on the details how the 2x transfer block is connected to the truss, and how the 2x ledger is connected to that transfer block. 9. Sheet I-5001; Detail 5: Please indicate on this detail if the box beam (joist) spans from wall to wall, what connection is used at the 2x2 metal angle to the wall, and what is used to connect the box beam to the 2x2 metal angles. 10. General: Please provide written responses to all review comments. |
| 02/09/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/20/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The urinal does not appear to have a partition; verify that the men's restroom is intended to be a single-occupant restroom with a lockable door. Reference: Exception (1), Section 405.3.4, IPC 2012. 2. Verify that the specified metered faucets for the restroom lavatories will dispense a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 3. Verify that the discharge from the specified dishwasher (Hobart LXeR) will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012. 4. The floor sink that receives the discharge from the ice bin (10880) and the ice machine (10813) connects to the sanitary waste system. Why is it included in the grease interceptor calculations? Reference: Section 107.2.1, IBC 2012. 5. Provide separate indirect waste pipes for the ice machine and for the ice bin to protect against cross-contamination or fouling. Reference: Section 801.2, IPC 2012. 6. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 7. Hand sinks 10581 and 17809 directly connect to the sanitary waste system. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson. |
| 02/20/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Explain why the existing mechanical equipment schedule shows HP-2 and HP-3 are different from the units shown on the approved shell package drawings. New units will require heating and cooling load calculations to verify that they have the appropriate capacities. Reference: Section 107.2.1, IBC 2012 and Section C403.2.2, IECC 2012. 2. Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012. |
| 02/20/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T18CM00718 - Starbucks Tenant Improvement Plans (1st Review) 2807 N. Campbell Avenue TRANSMITTAL DATE: February 20, 2018 DUE DATE: February 28, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the building plans but cannot approve them at this time. The proposed modifications to the interior do not affect any zoning requirements and the use of the building and site is not changing. In addition, the building plans must be approved by the PDSD commercial plans reviewers before zoning can approve the plans. 2. COMMENT: The patio area was not defined on the DP as shown on this TI plan. The patio are must be adjusted on the plan to be directly with the footprint area, see Redlines on sheet G-0005. If the patio area is larger than the area redlined the Development Package will have to be revised before the T.I can be approved. 3. COMMENT: Once the plans have been approved by all Commercial Plans reviewers and no site changes are made that affect zoning requirements, zoning will stamp and sign the building plans as it pertains to the zoning review purview. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email at David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov |
| 02/20/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/26/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |