Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM00693
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/29/2018 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
01/29/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
01/29/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide the following information. #1. A lighting plan that shows the new luminaire and switching locations and a complete luminaire schedule including 2012 IECC compliance. #2. A complete panel schedule. #3. Assign circuit and panel designations for the new and relocated outlets, devices, and lighting. Ref:2012 IBC sec 107.2.1, 2011 NEC art 408.4, 2012 IECC, City of Tucson Commercial Plan Submittal Requirements. |
01/29/2018 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
01/29/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/29/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/29/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The distance from the hot water source to the most distant load is greater than fifty-feet. 2. Show how the waste from the glass washer will be have a temperature lower than 140 degrees Fahrenheit. |
01/29/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/29/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |