Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM00604
Parcel: 11516023B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM00604
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 2; Sheet G100; Plumbing Fixtures: The note was removed as requested, but the fixture table should indicate a drinking fountain is required. Add a note that the refrigerator with an accessible water source and drinking cups is provided.
2. Previous Comment 13; Sheet A500; Detail 5: The boxed note that references Detail 14/A500 was not changed. Please revise the reference.
3. Previous Comment: Please provide written responses to all review comments.
02/16/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/16/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations that justify the capacities of the two new rooftop AC units specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.