Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM00604
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/16/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 2; Sheet G100; Plumbing Fixtures: The note was removed as requested, but the fixture table should indicate a drinking fountain is required. Add a note that the refrigerator with an accessible water source and drinking cups is provided. 2. Previous Comment 13; Sheet A500; Detail 5: The boxed note that references Detail 14/A500 was not changed. Please revise the reference. 3. Previous Comment: Please provide written responses to all review comments. |
| 02/16/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/16/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide heating and cooling load calculations that justify the capacities of the two new rooftop AC units specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012. |