Permit Number: T18CM00604
Parcel: 11516023B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM00604
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2018 ANDREW CONNOR ZONING REVIEW Approved
01/25/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/25/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the sensor faucets for the lavatories are set to deliver a maximum of 0.25 gallons per operating cycle (e.g. 30-second shut-off at 0.5 GPM).
2. Provide thermostatic mixing valves listed to ASSE 1070 to supply tempered water to each lavatory.
01/25/2018 ACONNOR1 ENGINEERING REVIEW Passed
01/25/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G100; Life Safety Plan; Occupancy Load Table: The occupant load calculations for the storage area and the business area are not correct. Please revise. The Plumbing Fixture Table indicates the correct occupant load (38 total).
2. Sheet G100; Plumbing Fixtures Table: The note in this table indicates a hi-lo drinking fountain is required when the occupant load is more than 50. Please remove that note. A high/low drinking fountain or single point-of-use water dispenser (connected to a water line, but no drain necessary) is required on this project.
3. Sheet G100; Life Safety Plan: Please revise the occupant load at each exit for the new occupant load (see comment 1).
4. Sheet G100; Plumbing Fixtures Table: What do the asterisks in this table represent? Please verify.
5. Sheet G100; Accessibility Notes: Please revise Note 4 to the 2009 ICC/ANSI.
6. Sheet G100; Accessibility Notes: Please remove the ADA and ADAAG references in Notes 1 and 9.
7. Sheet G100; Project Data: The building is designated as a separated occupancy per the IBC 508.3. That would require fire resistance rated walls, doors, openings, and penetrations between the S-1 and B areas. The Wall Types indicated on Sheet A100 do not indicate that. Is this a separated occupancy? Please indicate the allowable area for this mixed use (per the IBC Section 508.3.2) if it is non-separated, or indicate fire resistance rated walls per the IBC Section 508.4 if it is separated.
8. Sheet G120; Accessibility Notes: Please remove the ADA and ADAAG from Notes A, D, and I.
9. Sheet A100; Legend: The Wall Types note references a schedule on Sheet A120. Please revise that reference.
10. Sheet A120; Reflected Ceiling Plan: Detail cuts at some interior walls reference 14/A500 and 15/A500. Please revise those references.
11. Sheet A500; Detail 1: Extend the section to the roof and show how the wall connects to the roof.
12. Sheet A500; Detail 2: A boxed note indicates to "Refer Structural for Continuation". There is no structural in this submittal. Please extend the section to the roof and show how the wall connects to the roof.
13. Sheet A500; Detail 5: A boxed note indicates "See Detail 14/A500 for Additional Information". There is no Detail 14/A500. Please revise.
14. General: Please provide written responses to all review comments.
01/25/2018 ROBERT SHERRY WATER REVIEW Completed
01/25/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/25/2018 JPEELDA1 FIRE REVIEW Approved
01/26/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved