Permit Number: T18CM00396
Parcel: 133165780

Address:
6500 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM00396
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2018 MARTIN BROWN FIRE REVIEW Approved
01/31/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A111; Plan 1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the interior and exterior elevation indicators.
2. Sheet A301; Plan 1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the exterior elevation indicators.
3. Sheet A303; Plan 1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the interior elevation indicators.
4. Sheet A303; Elevation 6: Per the ICC/ANSI Section 904.3.1, sales and service counters must be a maximum of 36" in height above the finish floor. Please verify and revise Elevation 6 as required.
5. Sheet A307; Plan 2: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the interior elevation indicators.
6. Sheet A307; Plan 1: Per the ICC/ANSI Figure 604.2, the centerline of the accessible water closet must be 16" to 18" from the face of the sidewall. Plan 1 indicates 1'-7" clear in the men's and women's restrooms. Please revise that dimension, and remove the word 'clear' from the dimension (the accessible watercloset in Elevation 24 indicates 1'-5". Please coordinate).
7. Sheet A313; Plan 3: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the interior elevation indicators.
8. Sheet A313; Elevation 2: Per the ICC/ANSI Section 904.3.1, sales and service counters must be a maximum of 36" in height above the finish floor. Please verify and indicate on the elevation. In addition, reference Elevation 1 on Sheet ASV1 for this counter.
9. Sheet A313; Plan 1: Per the IBC Section 1108.2.9.1, 5% of the total number of dining surfaces (minimum 1) for food or drink shall be accessible. Please add a note that references Sheet ASB1 to verify that requirement is met.
10. Sheet A313; Section 4: Please finish the upper note for the bulkhead connection.
11. Sheet A313; Section 4: Please indicate the metal stud spacing (or add a reference) in the note, and finish the note.
12. Sheet A313; Section 4: Please finish the CJ note.
13. Sheet A331; Plan 1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the interior elevation indicators.
14. Sheet A331; Plan 1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the interior elevation indicators.
15. Sheet A332; Plan 4: Please revise the plan title to 'Office Finish Plan'.
16. Sheet A341; Plan 1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the interior elevation indicators.
17. Sheet A502; Detail 26: Please revise the lower boxed note so it is legible.
18. Sheet A502; Detail 26: The last note references Detail 10/A611. Please revise the reference.
19. Sheet ASB1; Plan 2: Per the IBC Section 1108.2.9.1, 5% of the total number of dining surfaces (minimum 1) for food or drink shall be accessible. Please indicate the calculation on this plan for the required number of accessible seats and dining surfaces. Indicate those on the plan by showing the 30" x 48" clear floor space (see ICC/ANSI Figure 305.3 and Section 902.2) and the top of the dining surface above finish floor (see ICC/ANSI Section 902.4).
20. Sheet ASV1; Elevation 1: Per the ICC/ANSI Section 904, indicate on the elevation the height and length of the sales/service counter (Section 904.3.1) required by this section for accessibility.
21. Sheet S521 (Detail 18); Structural Calculations (Page 16): The calculations indicate the plate at the wall to be 3/8" thick, while the detail indicates 5/16" thick. Please coordinate.
22. Structural Calculations; Page 22: Where does this detail occur? No detail on Sheet S521 was a match for the detail in the calculations.
23. General: Please provide written responses to all review comments.
02/05/2018 ROBERT SHERRY WATER REVIEW Completed
02/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the specified sensor faucet for the public lavatories has an automatic time-out so that it will dispense a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Coordinate details 3/P501 and 8/P501with detail 4/P501 to show the installation of the thermal expansion tank between the water heater and the required shut off valve. Reference: Sections 303.2 and 607.3.2, IPC 2012.
3. Provide a drain water tempering kit for the dishwasher (Hobart model LXeH) to ensure that the discharge from the dishwasher will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012.
4. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
5. Provide a downstream vent for the grease interceptor. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Sections 905.4 and 1003.9, IPC 2012.
6. A dishwasher may not discharge through a hydromechanical grease interceptor. Verify how the discharge from the dishwasher can be accommodated with the Pima County Regional Wastewater Reclamation Department. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
7. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
8. Verify that the Pima County Regional Wastewater Reclamation Department will allow the drain from the janitor's sink to bypass the grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
02/06/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide exhaust for the fitting rooms. Reference: Section 403.3 and Table 403.3, IMC 2012.
2. Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood (e.g. Turbochef oven). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Sections 403.3 and 507.2.2, IMC 2012.
3. Provide heating and cooling load calculations that justify the capacities of the new heating and cooling equipment specified for the project (AC-4/CU-4). Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.
02/14/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete compliance with the 2012 IECC for the revised interior lighting.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/22/2018 LPEREZ2 APPROVAL SHELF Completed
02/22/2018 LPEREZ2 OUT TO CUSTOMER Completed
02/22/2018 LPEREZ2 REJECT SHELF Completed