Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM00377
Parcel: 117067480

Address:
30 S 5TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM00377
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2018 ANDREW CONNOR ZONING REVIEW Approved
01/16/2018 ACONNOR1 ENGINEERING REVIEW Passed
01/17/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/17/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.
2. The dryer exhaust duct appears to have an equivalent length greater than 35-feet. If the dryer manufacturer allows the 35-foot length to be exceeded, show the make and model of the proposed dryer on the plans and provide a copy of the manufacturer's installation instructions. Reference: Section 504.6.4.2, IMC 2012.
3. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012.
01/17/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0.00; Code Analysis: A spa is identified as a "B" occupancy, and the retail portion is a secondary use. The total occupant load could be based on the gross square footage as a "B" occupancy. Please verify.
2. Sheet A0.00; Code Analysis: Please include on this sheet the calculations for the required plumbing fixtures using the IBC Table 2902.1.
3. Sheet A2.01; Floor Plan: Per the Code Analysis, this space has an occupant load of 20. This is a "B" occupancy type, and the IBC Section 2902.2 requires separate facilities for more than 15 occupants. Only one restroom is indicated on the plan. Please verify.
4. Sheet A2.01; Floor Plan: The plan indicates an accessible route from the restroom to the exit. Per the IBC Section 1016.3, indicate on the plan the exit access travel distance from the most remote point in this tenant space to the exit.
5. Sheet A2.02: Please add details on this sheet for the shower grab bars and the control/handshower location per the ICC/ANSI Section 608..
6. Sheet P2.01; Detail 1: Please extend the detail to the roof structure and indicate how the all thread rods connect at the structure.
7. General: Please provide written responses to all review comments.
01/17/2018 MARTIN BROWN FIRE REVIEW Approved
01/17/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/17/2018 ROBERT SHERRY WATER REVIEW Completed
01/17/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed