Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM00355
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/16/2018 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
01/16/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the ventilation calculations using Sections 403.3 and 403.6, IMC 2012. |
01/16/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/16/2018 | AHINES2 | ENGINEERING | REVIEW | Passed | |
01/16/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G0.0; Applicable Codes: Please remove the 2010 ADA Standards for accessibility, and add the 2009 ICC/ANSI A117.1. 2. Sheet A1.1A; RCP Plan: Note 24 (new exit sign) is indicated in two locations below Grid D and between Grids 7 and 8. Is the exit sign to the south located correctly? Please verify. 3. Sheet A1.1B; Ground Floor Plan: Note 7 (new wall) is indicated south of Grid 3 and between Grids D and E. Is this a wall? Please verify. 4. General: Please provide written responses to all review comments. |
01/16/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/16/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
01/16/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/16/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |