Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM00355
Parcel: 128100550

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM00355
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2018 ALEXANDRA HINES ZONING REVIEW Approved
01/16/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the ventilation calculations using Sections 403.3 and 403.6, IMC 2012.
01/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/16/2018 AHINES2 ENGINEERING REVIEW Passed
01/16/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G0.0; Applicable Codes: Please remove the 2010 ADA Standards for accessibility, and add the 2009 ICC/ANSI A117.1.
2. Sheet A1.1A; RCP Plan: Note 24 (new exit sign) is indicated in two locations below Grid D and between Grids 7 and 8. Is the exit sign to the south located correctly? Please verify.
3. Sheet A1.1B; Ground Floor Plan: Note 7 (new wall) is indicated south of Grid 3 and between Grids D and E. Is this a wall? Please verify.
4. General: Please provide written responses to all review comments.
01/16/2018 ROBERT SHERRY WATER REVIEW Completed
01/16/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/16/2018 MARTIN BROWN FIRE REVIEW Approved
01/16/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed