02/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
As per the previous electrical plan review comment for Outdoor Lighting Code compliance.
#1. The lighting area is 'E3' not 'E3A'. This will change the Lumen per Acre cap.
#2. Per section 104.2(1). Provide plans indicating the location on the premises, and the type of illuminating devices, fixtures, lamps, supports, reflectors, and other devices, and a luminaire schedule as outlined in sub-section 104.2.1.
#3. Full compliance with section 104.2.1 (1- thru- 3).
#4. Per section 104.2.2. Include special inspection note.
#5. Provide compliance with section 402.1. ( Color Temperature ).
Ref: 2012 IBC sec 107.2.1, 2012 Outdoor Lighting Code, City of Tucson ordinance # 10963, 2011 NEC.