Permit Number: T18CM00351
Parcel: 133233570

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM00351
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide complete compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE for exterior lighting. Can be printed or downloaded from www.tucsonaz.gov/pdsd. See section 104.