Permit Number: T18CM00327
Parcel: 10509546B

Address:
78 W RIVER RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM00327
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2018 MGAYOSS1 ZONING REVIEW Needs Review
01/12/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/12/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The developed length of the hot water pipe from the water heater to the furthest lavatories appears to be in excess of fifty-feet. Reference: Section 607.2, IPC 2012.
01/12/2018 MGAYOSS1 ENGINEERING REVIEW Passed
01/12/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G0.0; Code Data (Occupancy Calculations): Please provide the calculations for the occupant load on this sheet.
2. Sheet G0.0; Code Data (Occupancy Group): The occupancy group is listed as B, but the Zoning Data indicates it is retail. Please coordinate.
3. Sheet A1.0; Floor Plan: Note 7 indicates new millwork. The plumbing Sheets P1.1 and P1.2 indicate a water dispenser in the same location as the new millwork. Provide information for the new millwork, and indicate on the drawings the point of use water dispenser is accessible is located on top of the millwork.
4. Sheet A3.1; Elevations 110 N, 111 N, and 112 N: Please indicate the vertical grab bar per the ICC/ANSI Figure 604.5.1.
5. Sheet A4.1; Elevation 3A: The plan indicates this counter is 30" A.F.F., while the Elevation indicates 2'-4" (28"). Please coordinate.
6. General: Please provide written responses to all review comments.
01/12/2018 ROBERT SHERRY WATER REVIEW Completed
01/12/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/12/2018 JVINCEN1 FIRE REVIEW Approved
01/16/2018 QJONES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2018 QJONES1 APPROVAL SHELF Completed
01/16/2018 QJONES1 OUT TO CUSTOMER Completed
01/16/2018 QJONES1 REJECT SHELF Completed