Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM00327
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/12/2018 | MGAYOSS1 | ZONING | REVIEW | Needs Review | |
01/12/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
01/12/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The developed length of the hot water pipe from the water heater to the furthest lavatories appears to be in excess of fifty-feet. Reference: Section 607.2, IPC 2012. |
01/12/2018 | MGAYOSS1 | ENGINEERING | REVIEW | Passed | |
01/12/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G0.0; Code Data (Occupancy Calculations): Please provide the calculations for the occupant load on this sheet. 2. Sheet G0.0; Code Data (Occupancy Group): The occupancy group is listed as B, but the Zoning Data indicates it is retail. Please coordinate. 3. Sheet A1.0; Floor Plan: Note 7 indicates new millwork. The plumbing Sheets P1.1 and P1.2 indicate a water dispenser in the same location as the new millwork. Provide information for the new millwork, and indicate on the drawings the point of use water dispenser is accessible is located on top of the millwork. 4. Sheet A3.1; Elevations 110 N, 111 N, and 112 N: Please indicate the vertical grab bar per the ICC/ANSI Figure 604.5.1. 5. Sheet A4.1; Elevation 3A: The plan indicates this counter is 30" A.F.F., while the Elevation indicates 2'-4" (28"). Please coordinate. 6. General: Please provide written responses to all review comments. |
01/12/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/12/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/12/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
01/16/2018 | QJONES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/16/2018 | QJONES1 | APPROVAL SHELF | Completed |
01/16/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
01/16/2018 | QJONES1 | REJECT SHELF | Completed |