Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM00324
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/12/2018 | MGAYOSS1 | ZONING | REVIEW | Passed | Reviewer: Maria Gayosso 1/12/18 Recommended applicant to consult with Hisotric Preservation staff. |
01/12/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
01/12/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
01/12/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
01/12/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/12/2018 | ROBERT SHERRY | WATER | REVIEW | Passed | |
01/12/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/16/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/16/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please include an electrical line diagram to clarify where the dedicated 120 volt power for the EMS is deived from. Include conduit, conductor sizes and types, breaker panel and circuit designation, panel location, panel schedule with load calc. Ref: 2012 IBC sec 107.2.1, 2011 NEC |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/20/2018 | QJONES1 | APPROVAL SHELF | Completed |
03/20/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
03/20/2018 | QJONES1 | REJECT SHELF | Completed |