Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM00324
Parcel: 117200270

Address:
260 S CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM00324
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2018 MGAYOSS1 ZONING REVIEW Passed Reviewer: Maria Gayosso
1/12/18
Recommended applicant to consult with Hisotric Preservation staff.
01/12/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/12/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/12/2018 LOREN MAKUS ENGINEERING REVIEW Passed
01/12/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/12/2018 ROBERT SHERRY WATER REVIEW Passed
01/12/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/16/2018 MARTIN BROWN FIRE REVIEW Approved
01/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please include an electrical line diagram to clarify where the dedicated 120 volt power for the EMS is deived from. Include conduit, conductor sizes and types, breaker panel and circuit designation, panel location, panel schedule with load calc.
Ref: 2012 IBC sec 107.2.1, 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
03/20/2018 QJONES1 APPROVAL SHELF Completed
03/20/2018 QJONES1 OUT TO CUSTOMER Completed
03/20/2018 QJONES1 REJECT SHELF Completed