Permit Number: T18CM00277
Parcel: 136290020

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM00277
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2018 MARTIN BROWN FIRE REVIEW Approved
01/23/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S3; Spread Footing Schedule: A footing F2 is listed in this schedule, but no structural calculation was provided for this footing. Please verify.
2. Sheet S4; Spread Footing Schedule: The footing in the schedule is marked as F2, while the framing plan indicates F1. Please revise.
01/29/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref: Plan Sheet 'E4.0', thru 'E5.2'. Revise the VOLTAGE DROP CALCULATIONS tables and line diagrams so that the feeder sizes shown on the line diagrams are identified with a mark that correlates with the feeder columns on the tables. This will help inspectors in the field clearly identify the appropriate feeder sizes called out between the equipment.
Ref:2012 IBC sec 107.2.1, 2011 NEC