Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T18CM00277
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/17/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/23/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S3; Spread Footing Schedule: A footing F2 is listed in this schedule, but no structural calculation was provided for this footing. Please verify. 2. Sheet S4; Spread Footing Schedule: The footing in the schedule is marked as F2, while the framing plan indicates F1. Please revise. |
01/29/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref: Plan Sheet 'E4.0', thru 'E5.2'. Revise the VOLTAGE DROP CALCULATIONS tables and line diagrams so that the feeder sizes shown on the line diagrams are identified with a mark that correlates with the feeder columns on the tables. This will help inspectors in the field clearly identify the appropriate feeder sizes called out between the equipment. Ref:2012 IBC sec 107.2.1, 2011 NEC |