Review Details: COMMERCIAL - NEW
Permit Number - T18CM00270
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/17/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/24/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-0; Building Code Analysis: This sheet indicates the maximum dead end length (corridor) is 20 feet. Per the IBC Section 1018.4(2), the maximum allowable length is 50 feet. Please revise. 2. Sheet A-0; Building Code Analysis: This sheet indicates the exterior walls meet a fire resistance rating of one hour per the IBC Table 721.1(2). Does this wall need to be rated per the IBC Tables 601 or 602? Please verify. 3. Sheet A-0; Building Code Analysis: This sheet indicates the allowable building area is 9000 SF, and an area increase is not applicable. The IBC Section 506.3 allows a 300% increase in area if the building is sprinklered. This would increase your allowable area to: (3 x 9000) + 9000 = 36,000 SF. Please revise the drawing. 4. Sheet A-0; Building Code Analysis: This sheet indicates the allowable building height is one story (40 feet). The IBC Section 504 allows two stories (60 feet) if the building is sprinklered. Please revise the drawing. 5. Sheet A-1; Elevation 6: A Section A-A is cut through the door head. Where is this section located? Is it Section 7? 6. Sheet A-1; Detail 8: Should Door D (at the women's restroom) be included with Doors C and E? Please verify. 7. Sheet A-2; Exterior Elevations: Please add the Section cut 2/A3.1 on the wall elevation (front wall). 8. Sheet A-3: On the upper left side of this sheet, a note describing the roof system is indicated. If this note is to remain on this sheet, please darken the font. 9. Sheet A3.1: Please add in the Wall Section End Wall (Storefront) title the number 1. 10. Sheet S0 (General Notes); Structural Calculations (Code Check): The Code Check indicates the minimum bearing depth of the foundation is 18 inches. This minimum depth was not located in the General Notes. Please add this to the General Notes. 11. Sheet S1.2; Detail 1: Please indicate on the detail the maximum allowable height of the lightpole for this foundation. 12. Sheet S2; Detail 8: The Detail references 9/S1 for the tube column. Please revise that reference. 13. General: Please provide a site plan that indicates the distance from the building exterior walls on all sides to adjacent buildings or property lines. Verify whether the exterior walls are required to be fire resistance rated or not (see Comment 2). 14. General: Please provide written responses to all review comments. |
| 01/29/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a site drawing showing the size, route, and slope of the building sewer and the location of its connection to the public sewer. Reference: Section 107.2.1, IBC 2012. 2. Show that the cycle times for the metering faucets in the lavatories will be adjusted to limit the water delivery to a maximum of 0.25 gallons per cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. 3. The cycle time for the metering faucets for the lavatories shall be at least 10-seconds for accessibility. Reference: Section 606.4, ICC/ANSI A117.1-09. 4. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 5. Disinfection of the potable water system shall be per Section 610.1, IPC 2012. 6. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. 7. Revise the roof drain calculations to include the effect of any vertical walls that can divert rainfall onto the roof. Reference: Section 1106.4, IPC 2012. 8. Scuppers are not equivalent to horizontal pipes; provide the hydraulic calculations used to determine the size of the scuppers. Based on a head of 2" and a rainfall rate of 3"/hour, a 6"-wide scupper can only accommodate 1530 square feet of roof (47 GPM). Reference:1101.7 and 1108.3, IPC 2012. |
| 01/30/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify the areas and U-values used in COMcheck for the overhead door on the north wall and the two hollow metal doors on the east wall of the building as shown on the drawings and in the specifications. Reference: Section 107.2.1, IBC 2012. 2. Clarify how the projection factor was calculated for the windows and glazed door. With a projection of 5'-0" over most of the glazed areas, a PF of 1.30 results in a glass height on 3.8-feet below the projection and a PF of 0.03 results in a glass height of 167-feet below the projection. Reference: Section 107.2.1, IBC 2012. 3. Specify the maximum acceptable NFRC-certified U-values and solar heat gain factors (SHGC) for the storefront and glazed doors on the drawings. Use the same values for the COMcheck calculations or utilize the default values shown in Tables C303.1.3(1), C303.1.3(2) and C303.1.3(3). Reference: Section C303.1.3, IECC 2012. 4. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012. 5. Clarify how excess outside air will be relieved from the building during economizer operation without recirculation of the relief air. Reference: Section C403.3.1.1.4, IECC 2012. 6. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson. 7. Detail 4/M-1.1 calls for a smoke detector to be mounted to the supply air duct of each rooftop unit. Detail 5/M-1.1 states that a smoke detector will be factory-installed in the return duct of each rooftop unit. Are both smoke detectors being installed or just one? Reference: Section 107.2.1, IBC 2012. |
| 01/30/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan. The development package is not a substitute for a complete site plan. Reference: Section 107.2.5, IBC 2012. 2. Provide the size of the backflow preventer associated with the water meter. Reference: Section 107.2.1, IBC 2012. |
| 02/07/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide full compliance with the Tucson/Pima County Outdoor Lighting Code. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. See Section 104 for plan submittal requirements. |
| 02/07/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T18CM00270 - New Building (Retail - General Merchandise) Building Plan Review (1st Review) AutoZone 3271 E Valencia Road TRANSMITTAL DATE: February 7, 2018 DUE DATE: February 9, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has done a cursory review of the building plans. Prior to a more comprehensive review by zoning the DP must be reviewed and approved prior to zoning approval of the building plans. While the cursory review did yield an indication that the building plans are consistent with what has been proposed and drawn on the DP (that has been submitted for review) zoning cannot approve the building plans at this time. While the building footprint is consistent with the footprint on the DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc.) zoning cannot approve the building plans until the Commercial Plans reviewer(s) have approved the building plans. 2. COMMENT: Zoning will review the building plans on the next submittal to assure consistency with the DP. If any changes are necessary to the building plans due to plan review comments that affect zoning requirements the DP will have to be revised to reflect the changes. Once the DP is approved by all reviewers and the building plans are approved by the Commercial Plans reviewers zoning can approve the building plans. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans |
| 02/21/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/01/2018 | BLARSON1 | OUT TO CUSTOMER | Completed |