Permit Number: T18CM00189
Parcel: 129020870

Review Status: Active

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T18CM00189
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2018 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW RECEIVED
01/09/2018 ANY 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Active
01/26/2018 JPEELDA1 FIRE REVIEW Approved
01/30/2018 ROBERT SHERRY WATER REVIEW Reqs Change Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (i.e. typically adjacent to the water meter). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf.
02/05/2018 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: 2744 E. Broadway Blvd.
T18CM00189
Building Plan (1st Review)

TRANSMITTAL DATE: February 5, 2018

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans were reviewed for compliance with DP17-0257 and appear to meet all requirements but until two plans sets are provided and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
02/05/2018 SSHIELD1 ZONING HC REVIEW Passed
02/21/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change Sheet A100. Roof and overflow drains refer to sheet A310. There is no sheet A310 provided in plans. Update reference or provide sheet A310. Roof drains are to be scuppered through sidewalk per TSM 7-01.4.1.E and TSM 10-01.4.4.F.

John Van Winkle