Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW - COMMERCIAL
Permit Number - T18CM00153
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2018 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 01/31/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Show the location, size and serial number of the water meter that will serve the addition. Show the location and size of the backflow preventer. Provide the total water demand that will be served by the meter. Reference: Section 107.2.5, IBC 2012 and Chapter XXVII, Article V, Section 27-72, the Tucson Code. |
| 02/06/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T18CM00153 Building Plan Review (1st Review) 4646 E 22nd Street TRANSMITTAL DATE: February 06, 2018 DUE DATE: February 07, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. While the building footprint and the site revisions are consistent with the approved DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the Commercial Plans reviewers have approved the building plans. 2. COMMENT: As of this building plan review the approved DP had not been scanned by PDSD records. Once the DP is scanned and available on line, zoning can review the building plans and reference the approved DP for consistency. It is assumed that the DP will be scanned by PDSD Records Section before the next re-submittal. However, if available, include as reference a copy of the approved and signed copy of the DP with the next submittal. If the re-submittal of the building plans is longer than two weeks from today a hard copy of the DP will not be required to be included with the next building plan re-submittal. 3. COMMENT: Zoning will review the building plans on the next submittal to assure that any revisions made to the building plans do not affect zoning requirements. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: |
| 02/07/2018 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Approved | |
| 02/12/2018 | JVWINKL1 | ENGINEERING | REVIEW | Reqs Change | Scupper main roof drains on south elevation through sidewalk for pedestrian access. City of Tucson Technical Standards Manual 7-01.4.1 E |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/12/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 03/12/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 03/12/2018 | QJONES1 | REJECT SHELF | Completed |