Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Permit Number - T18CM00128
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/24/2018 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T18CM00128 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. SITE PLAN: 1. Indicate the location of buildings, utility meters and gas, water, electric and sewer lines from property line to building, R106.1.1. Show the point of connection of proposed lines to the service lines for verifying correct sizes and necessary upgrades. STRUCTURAL PLANS: 1. Provide a complete roof framing plan with the addition ridge beam sized with appropriate load carrying capacity. Design roof structural members that support rafters as beams when the roof pitch is less than 3" to 12", R802.3. Or show roof structural members with rafter ties (or ceiling joists) and collar ties (ridge straps) when the roof pitch is equal or greater than 3" to 12", R802.3. SECTIONS - DETAILS: 1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray or rigid board tight to the roof sheathing), R806.5. This condensation control provision is necessary for code compliance, and may be a single layer of air-impermeable insulation, or layered with batt insulation for achieving the total required roof R-value. PLUMBING PLANS: 1. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Show a ¾" pipe to the new furnace and water heater. It may be reduced to ½" between the furnace and water heater. The extension from the dryer may not have sufficient size back to the meter if only ¾" without showing the complete system. ELECTRICAL PLANS: 1. Show the location of the Electrical Service Panel, E3404.12. 2. Protect all interior 15A & 20A proposed outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 01/29/2018 | ARUIZ1 | ENGINEERING | REVIEW | Needs Review |