Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM00084
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review 1. Sheet PV1.1; Section/Profile A and D: The City of Tucson allows Group U parking shade structures to be erected without any fire resistive rating provided the vertical structural supports have a fire separation distance of at least five feet (face of vertical support to face of existing structure/overhang), and the roof projection has a fire separation distance of at least 24 inches (face of roof projection to face of existing structure/overhang). The Section/Profile on this sheet indicates the new structure does not meet that criteria and must be fire resistive rated or moved further away from the existing structure. Please verify.
2. Sheet S2.0; Array Plan: The section cuts through the structure reference 1/S2.1 and 2/S2.1. Please revise those references.
3. Sheet S2.0; Array Plan: At the longer portion of the Array Plan, the match line indicates to "See Plan 2 This Sheet". Please revise the plan number at the shorter portion of the Array Plan to 2.
4. General: Please provide written responses to all review comments.
01/19/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/19/2018 KELLY LEE ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2018 ARUIZ1 OUT TO CUSTOMER Completed