Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T18CM00055
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/12/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/12/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the activity number for the revision of the storefront. [Initial comment: Demonstrate energy code compliance for the alterations to the building envelope based on the current code (replacement of the existing storefront). Specify the required U-factors and Solar Heat Gain Coefficients (SHGC) for the new storefront on the architectural drawings. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012.] 2. The heating and cooling calculations are not legible. [Initial comment: Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.] 3. Calculation of the required minimum ventilation for air handlers serving multiple zones requires the use of the calculations described in Sections 403.3.2.3.1 through 403.3.2.3.4, IMC 2012. Reference: Section 403.3.2.3, IMC 2012. [Initial comment: Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.] |
02/12/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | A vacuum relief valve is not a T&P vacuum relief valve even though it is covered by ANSI Z21.22. See the referenced section in the 2012 IPC. [Initial comment: Provide an approved vacuum relief valve for the scheduled bottom-fed water heater located above the fixture outlets. Reference: Section 504.2, IPC 2012.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/22/2018 | QJONES1 | APPROVAL SHELF | Completed |
02/22/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
02/22/2018 | QJONES1 | REJECT SHELF | Completed |