Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM00055
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM00055
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2018 JVINCEN1 FIRE REVIEW Approved
01/18/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet C1.1; Code Summary: Please revise the accessibility code to the 2009 ICC/ANSI A117.1.
2. Sheet C1.1; Minimum Plumbing Fixtures: Please indicate a drinking fountain is required, and the public drinking fountain is located within 300 feet of the tenant space.
3. Sheet ACC2; Accessibility Details 1: On the toilet sidewall, please indicate the dimension from the floor to the bottom of the vertical grab bar per the ICC/ANSI Figure 604.5.1.
4. Sheet A0.1; Demolition Notes: Note 13 was not located on the plan. Please verify.
5. Sheet A0.2: The City of Tucson requires all lettering (upper and lower case) to be an actual 3/32" in height. Please revise the drywall notes on the plan at the demolition note 1.
6. Sheet A1.1; Construction Plan: The new wall between the stockroom and the sales area has a wall symbol for the Wall Type Detail 2/A5.1, but has a Section cut 3/A5.1 on the plan. Please coordinate.
7. Sheet A1.1; Construction Plan Notes: Note 14 is indicated at the electrical service in Hall 101b in the Notes, and at Office 102 on the plan (as well as in Hall 101b). Please coordinate.
8. Sheet A1.1; Construction Plan Notes: Note 17 is indicated at Office 102 in the Notes, and at the Toilet Room on the plan. Please coordinate.
9. Sheet A1.1; Construction Plan Notes: Note 18 is indicated at the Fitting Room in the Notes, and at the Stockroom on the plan. Please coordinate.
10. Sheet A1.1; Construction Plan Notes: Note 19 is indicated at the Fitting Room in the Notes, and at an electrical outlet on the plan. Please coordinate.
11. Sheet A1.1; Construction Plan Notes: Notes 15 and 16 are indicated at the Hall 101b in the Notes, and at the Fitting Room on the plan (as well as in Hall 101b). Please coordinate.
12. Sheet A1.1; Construction Plan Notes: Notes 20, 21, 22, 24, and 25 were not located on the plan. Please verify.
13. Sheet A1.2; Floor Finish Notes: Note 13 was not located on the plan. Please verify.
14. Sheet A5.1 (Sections 1 and 2); Sheet A1.1 (Construction Plan): The wall studs on Sections 1 and 2 should reference the Construction Plan and Wall Type Schedule for wall stud size and spacing.
15. Sheet A5.1; Section 3: Please reference the wall stud size and spacing on Section 3 to the Wall Type Schedule on Sheet A1.1.
16. Sheet A5.1; Section 5: Please reference the wall stud size and spacing on Section 5 to the Wall Type Schedule on Sheet A1.1.
17. Sheet A6.1: This sheet was not reviewed, as it indicates "For Reference Only".
18. General: Please provide written responses to all review comments.
01/26/2018 ROBERT SHERRY WATER REVIEW Completed
01/26/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the alterations to the building envelope based on the current code (replacement of the existing storefront). Specify the required U-factors and Solar Heat Gain Coefficients (SHGC) for the new storefront on the architectural drawings. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.
3. Keynote 2 on sheet M1.0 calls for the condensate drain to be extended to the nearest roof drain. Verify that the condensate drain terminates over a primary roof drain, not a secondary roof drain. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
4. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
01/29/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
3. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater located above the fixture outlets. Reference: Section 504.2, IPC 2012.
02/02/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/12/2018 KROBLES1 APPROVAL SHELF Completed
02/12/2018 KROBLES1 OUT TO CUSTOMER Completed
02/12/2018 KROBLES1 REJECT SHELF Completed