Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18BU00690
Parcel: 121050220

Address:
5548 E GRANT RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T18BU00690
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2019 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed
02/22/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T18BU00690

1) Existing building is impacted by a FEMA flood Zone AH. Proposed tenant improvement is a substantial improvement as it exceeds 50% of the building value as defined by Chapter 26 of the Tucson City Code
2) The building will need to be floodproofed following FEMA regulations. See following link https://www.fema.gov/media-library/assets/documents/34270
3) The option exists to reduce the value of the improvements such that they do not exceed 50% of the building cost. Another option is to attempt an elevation certificate to potentially remove the structure from the floodplain
4) A floodplain use permit will be required for any work conducted

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
02/22/2019 MASHFOR1 FIRE REVIEW Approved
02/22/2019 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/22/2019 KROBLES1 OUT TO CUSTOMER Completed