Permit Number: T18BU00658
Parcel: 10922452A

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T18BU00658
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2018 ALEXANDRA HINES ZONING REVIEW Approved
12/03/2018 AHINES2 ENGINEERING REVIEW Passed
12/05/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. The site plan specifies that the shade structure is to be constructed under separate permit; the column details show columns for the shade structure; please provide construction plans for the shade structure for approved design of the footings.
2 Specify the occupant load for the pool area and determine the required number of exits. Specify panit hardware where the occupant load exceeds 50 persons.
3. Provide a hi/low drainkng fountain for use by standing persons and poeple in wheel chair.

Please provide written comments to plan review comments.
12/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change PLAN REVIEW COMMENTS FOR T18BU00658
Please address the following electrical plan review comments. Also provide a written response.
#1. Provide GFI protected branch circuits pool lighting and pool pumps as required per NEC 680.21C, 680.23.
#2. Provide a wiring detail for the Emergency shut off controls for the Spa.
#3. Provide a complete grounding detail for the pool and associated electrical equipment, including exposed metallic parts and equipment, ladders, etc.
#4. Identify the panel feeding the new pool panel. Provide a panel schedule and load calcs.
#5. Provide a wiring diagram for the pool lighting,
#6. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd.
Ref; 2012 IBC sec 107.2.1, 2011 NEC art 680, Tucson Outdoor Lighting Code.
12/14/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/14/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2018 AVAUGHN1 APPROVAL SHELF Completed
12/19/2018 AVAUGHN1 OUT TO CUSTOMER Completed
12/19/2018 AVAUGHN1 REJECT SHELF Completed