Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18BU00644
Parcel: 99999999A

Address:
4050 E BENSON HY

Review Status: Completed

Review Details: WALLS

Permit Number - T18BU00644
Review Name: WALLS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2018 NICHOLAS ROSS ZONING REVIEW Approved
11/29/2018 NROSS1 ENGINEERING REVIEW Passed
11/29/2018 NROSS1 NPPO REVIEW Passed
11/30/2018 JVINCEN1 FIRE REVIEW Approved
12/03/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please provide structural calculations for the retaining walls. Sheet 2 of 9 shows a retaining wall detail that refers to ADOT SD 7.02 but that is not attached to the plan documents. The structural calculations must reflect the required reinforcing size and spacing as specified on the structural calculations. IBC 107.2.1.
2. Provide required special inspections for the retaining walls.