Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/23/2018 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Reqs Change Below are the BRC comments on the authorized repair submittal for COT ID# 555 at 298 South Freeway (T18BU00587).

Sheet 1 of 4
No comments.

Sheet 2 of 4
1. In 1st paragraph of boxed notes to right of Scope of Work box, add reference to Paragraph 10.4 of Stipulation that governs OSHA-mandated safety alterations.

2. For 13th & 14th paragraphs of Scope of Work, please add a paragraph for each, in the standard format, so the first is to “remove” and the second is to “install” (and assuring that dimensions conform with details related to comments #1 & #2 on Sheet 4).

3. After 15th paragraph or in other appropriate location of Scope of Work, add paragraph to reflect installation of safety cable guide

4. Add Side View Elevation or other appropriate view (including depiction of light fixtures) that shows dimensions from grade to respective bottoms of column mounted and upper access ladders;

Sheet 3 of 4
No comments.

Sheet 4 of 4

1, Add detail for column mounted ladders, including mounting detail, clarifying any dimensional differences between the existing and new ladders and showing distance from grade to bottoms and tops of ladders..

2. In Upper Access Ladder, clarify any dimensional differences between existing and new

3. In Safety Cable Guide & LAD-SAF Mounting Detail, revise to show ladder rungs as new (instead of existing and to remain)

4.. Provide overall length of installed cable in Side View Elevation or other appropriate view.

5. Provide detail of safety cable upper mounting bracket (if 3M, manufacturer’s technical data sheet is sufficient).

6. Provide detail of safety cable lower mounting bracket (if 3M, technical data sheet is sufficient).

7. Provide detail of safety cable guide (if 3M, manufacturer’s technical data sheet is sufficient).

8. Provide detail of sleeve that attaches to safety cable ((if 3M, technical data sheet is sufficient)..

9. Provide manufacturer’s technical data sheet on safety cable, if available.

10. Provide detail on how safety cable attaches to upper and lower mounting brackets..

FIN.