Permit Review Detail
Review Status: Completed
Review Details: POOL - COMM MODEL
Permit Number - T18BU00442
Review Name: POOL - COMM MODEL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLAN REVIEW COMMENTS Please address the following electrical plan review comments. Also provide a written response. #1. Provide GFI protected branch circuits pool lighting and pool pumps as required per NEC 680.21C, 680.23. #2. Provide a wiring detail for the Emergency shut off controls for the Spa. #3. Provide a complete grounding detail for the pool and associated electrical equipment, including exposed metallic parts and equipment, ladders, etc. #4. Identify the panel feeding the new pool panel. Provide a panel schedule and load calcs. #5. Provide a wiring diagram for the pool lighting, #6. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. Ref; 2012 IBC sec 107.2.1, 2011 NEC art 680, Tucson Outdoor Lighting Code. |
| 12/14/2018 | AVAUGHN1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 12/14/2018 | AVAUGHN1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |