Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18BU00199
Parcel: 141220250

Address:
9095 S RITA RD

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T18BU00199
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/14/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Plans with "white out" are not acceptable.
2. Provide a gas piping plan; show the location on the gas meter.
3. Provide coodination drawings for the utilities (gas, water, sanitary drain, etc.) provided with the buildings.
4. How is the pool heater vented?
05/16/2018 LPEREZ2 BUILDING-COMMERCIAL REVIEW Needs Review