Permit Number: T18BU00199
Parcel: 141220250

Address:
9095 S RITA RD

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T18BU00199
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2018 MMORENO1 ZONING REVIEW Passed
04/11/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1.Provide a complete electrical plan, including:
(a) Complete grounding and bonding detail.
(b) Line diagram for the existing service to the pool panel, include load calcs.
(c) Is the pool Panel new or existing?
(d) Provide full compliance with the Tucson/Pima County Outdoor Lighting Code for all the exterior lighting including the pool luminaires.
(e) Provide an electrical floor plan of the pool equipment room indicating the locations of all the electrical equipment.
Ref: 2012 IBC 107.2.1, 2011 NEC
04/11/2018 MARTIN BROWN FIRE REVIEW Approved
04/11/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a mechanical design by an Arizona registrant.
2. Verify the proposed location of the gas meter.
04/11/2018 MMORENO1 ENGINEERING REVIEW Passed
05/14/2018 KROBLES1 ADA REVIEW Passed
05/14/2018 KROBLES1 BUILDING-COMMERCIAL REVIEW Needs Review
05/14/2018 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed