Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T18BU00199
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2018 | MMORENO1 | ZONING | REVIEW | Passed | |
| 04/11/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1.Provide a complete electrical plan, including: (a) Complete grounding and bonding detail. (b) Line diagram for the existing service to the pool panel, include load calcs. (c) Is the pool Panel new or existing? (d) Provide full compliance with the Tucson/Pima County Outdoor Lighting Code for all the exterior lighting including the pool luminaires. (e) Provide an electrical floor plan of the pool equipment room indicating the locations of all the electrical equipment. Ref: 2012 IBC 107.2.1, 2011 NEC |
| 04/11/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/11/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a mechanical design by an Arizona registrant. 2. Verify the proposed location of the gas meter. |
| 04/11/2018 | MMORENO1 | ENGINEERING | REVIEW | Passed | |
| 05/14/2018 | KROBLES1 | ADA | REVIEW | Passed | |
| 05/14/2018 | KROBLES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 05/14/2018 | KROBLES1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |