Permit Number: T18BU00148
Parcel: 105100080

Address:
221 E WETMORE RD

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T18BU00148
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Since the permit scope is for the foundations design and detail, the design professional in responsible charge has signed, sealed, and dated all "Group P" sheets that provide the various structures and their sections/details. Are calculations required to be reviewed by the City of Tucson for those structures? Please clarify. Include a statement on the Cover Sheet and other structural sheets (SF305, SF306, and SF345) indicating the scope of the structural calculations and drawings.
2. General: All structural sheets to be reviewed indicate "Preliminary Not For Construction". This note must be removed for the review by the City of Tucson to continue.
3. Sheet SF305; Elevation 1: The footing size indicates to "See Footing Schedule". Please add the sheet reference to that note.
4. Sheet SF306; Typical Anchor Detail 3: Note 6 indicates to see Drawing P310 and AP Fab. drawings for the standpipe base plate details. Please provide that information or a sheet reference.
5. Sheet SF306; Typical Anchor Detail 3: Note 7 indicates to see the Column Table for slide support base plates. Please add a sheet reference to that note.
6. Sheet SF345: Are these details for the column, base plate, and anchor design only? Please verify.
7. General: Please provide written responses to all review comments.
04/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/09/2018 LPEREZ2 ENGINEERING REVIEW Needs Review
04/09/2018 LPEREZ2 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/09/2018 LPEREZ2 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/09/2018 LPEREZ2 OUT TO CUSTOMER Completed