58 E 5TH ST

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T17PI00039
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2017 GARY WITTWER DOT LANDSCAPE REVIEW Denied I see that you reduced the understory planting along 7th for pedestrian access to the sidewalk - thank you. Please do the same for planting between curb and sidewalk along 5th.

You are removing 8 Blue Palo Verde stating they are too close to the curb, and yet you are coming back in planting large tree 2' off the curb - and 5' off the building. ?????

You will need to add TDOT's standard notes for planting in the ROW. Please call or e-mail me for those. 837-6618
gary.wittwer@tucsonaz.gov

Please submit an irrigation plan - see notes for planting in ROW for irrigation requirements.
10/30/2017 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change Please see redline comments.

Redline drawing sent to Derek Willson on 10-30-17
10/30/2017 ZELIN CANCHOLA DOT TRAFFIC REVIEW Reqs Change October 30, 2017

SUBJECT: 7th Avenue Commons
PIA Plan T17PI00039

PROJECT REVIEWER: Zelin Canchola,
TDOT Review Section

DOT Review Section has reviewed the PIA Plan for Traffic Engineering. The proposed striping and signing is acceptable. However the width of the roadway travel lanes does not meet minimum standard of 12 feet. Eliminate angled parking on the east side of the road on 7th Avenue. Add/maintain parallel parking along east side of 7th Avenue.

1. Add type and size of striping for the parking. 4 inch is typical; with thermoplastic paint.

2. Add new Stop sign at North Echols Ave and 5th Street. Restore or replace street name signs.

3. No parking will be allowing on Echols Ave. Install No Parking signs.

4. Add General notes for pavement marking plans from PCDOT and TDOT Traffic Engineering division Sheet 2-1 (Pavement marking design manual)

If you have any questions I can be reached at 837-6659 or zelin.canchola@tucsonaz.gov
11/01/2017 ERNIE ENCINAS DOT_ELEC REVIEW Approved NO FURTHER COMMENTS - PAUL BURTON 10/31/17
11/13/2017 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
11/13/2017 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed