Plan Number: T17PI00037
Parcel: Unknown

Review Status: Completed

Review Details: PIA - RESUBMITTAL

Plan Number - T17PI00037
Review Name: PIA - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2018 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Denied
02/22/2018 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
02/22/2018 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Completed
02/22/2018 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Completed
02/22/2018 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
02/22/2018 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Completed
02/22/2018 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
02/22/2018 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Completed
02/27/2018 ZELIN CANCHOLA DOT TRAFFIC REVIEW Approved
02/28/2018 GARY WITTWER DOT LANDSCAPE REVIEW Approv-Cond The location I am concerned about is the Mainline crossing at Via Bombackas. Please show that it will be placed in ductile iron pipe and the the owner will become part of Blue Stake.
03/19/2018 RICHARD LEIGH DOT ENGINEERING REVIEW Approv-Cond March 19, 2018


SUBJECT: La Estancia De Tucson Kolb Road/Camino Boleadoras

PROJECT REVIEWER: Richard Leigh, TDOT Engineering Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and recommend a conditional approval. The following comments need to be addressed and plans revised prior to submitting mylar plans set for final approval. Please submit a PDF copy of the revised plan set prior to submitting mylars.

1. Sheet 3: Label all ADOT standards referenced with current ADOT standards.

2. Sheet 3, Detail 6: Verify that referenced details are labeled correctly.

3. Sheet 4: Reference detail for SD1 storm drain connection into RCBC culvert.

4. Sheet 4: Provide rock riprap details (rock size, depth and fabric details) for drainage swales located at Sta.58+39.50, RT & LT, (Camino Boledoras).

5. Provide RCP pipe class for storm drain laterals.

If you have any questions, I can be reached at 837-6647 or emailed at Richard.Leigh@tucsonaz.gov.
03/21/2018 TWOLFGA1 PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
03/21/2018 TWOLFGA1 PIA COORDINATOR OUT TO CUSTOMER Completed
07/13/2018 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Completed